Heat Engineer Logo
HEATENGINEER
Heat loss reports for engineers
Log In
Our Locations
Lancashire OfficeFirst HouseShuttleworth Mead Group12a Meadway PadihamBB12 7NG
Oxfordshire OfficeHeat Engineer Software Ltd46 Market SquareWitneyOX28 6AL
Devon OfficeMoorlands House North RoadOkehamptonDevonEX20 1BQ
Yorkshire OfficeThe Craggs Country Business ParkNew Road, Cragg Vale, Hebden Bridge, West YorkshireHX7 5TT
Heat Engineer LogoCyber Essentials Logo

Company Information

Company Registration Number09637929VAT Number217 2465 20

Connect With Us

AboutOur SoftwareTrainingPrivacy PolicyTerms and Conditions
Copyright ©2017-2025 Heat Engineer Software Ltd. All Rights Reserved.
Back to Blog
Technical

Understanding of EN 12831-1:2017 — Ventilation Heat Loss

01/06/2025
4 min read

Written by Richard Cartwright
Founder and CTO at Heat Engineer Software Ltd

Understanding of EN 12831-1:2017 — Ventilation Heat Loss
Contents
  • Abstract
  • Summary
  • Introduction
  • Why does the sum of room heat losses exceed the building heat loss?
  • Illustrating a building with Zone control with TRV’s
  • An incorrect representation
  • Pressure-driven internal air movement (even with equal temperatures)
  • Internal air movement does not disappear just because temperatures equalise.
  • Illustration of an open zone system with no TRV’s.
  • Still confused? Why your intuition says this, but physics says that.
  • What intuition tells us
  • What physics actually says
  • The critical distinction
  • Why controls don’t change this

Abstract

This document explains a commonly misunderstood outcome of BS EN 12831-1:2017: why the sum of individual room heat losses is greater than the total building (or zone) heat loss, particularly for ventilation and infiltration.

EN 12831-1 includes a fi-z factor specifically for wind-driven ventilation/infiltration part of sizing heating. The fi-z factor can have a value of '1' where 100% of the wind driven ventilation/infiltration is included, or '0.5' where just 50% of this is included.

For sizing a room heat emitter, the worst case is when the room is facing windward and all this ventilation/infiltration heat loss should be allowed for (fi-z = 1). However, for the central plant sizing worst case it only sees about half of rooms with its worst case, while the other half are on the leeward without this ventilation/infiltration heat loss. Consequently for sizing the central plant capacity a halving of the wind driven ventilation/infiltration heat loss component is typically used (fi-z = 0.5).

Summary

The key reason is that EN 12831 sizes rooms and the building heat source for different design purposes.

At room level, the standard deliberately applies worst-case assumptions. Each room heat emitter must be capable of covering:

  • Heat lost directly to outside via infiltration and ventilation, and
  • Heat carried out of the room by air moving to adjacent spaces.

For this reason, no reduction factor is applied to room ventilation heat losses (Equation 17). This ensures that emitters are robustly sized for unfavourable wind, pressure, and airflow conditions on the design day.

At zone or building level, EN 12831 only counts heat that actually leaves the building envelope. Air that moves between rooms remains within the heated zone and does not represent a net loss of heat to outside. To avoid double-counting internally retained heat, the standard applies the zone ventilation reduction factor fᵢ,z = 0.5 (Equation 16).

This approach applies regardless of heating control strategy:

  • Zoned systems with TRVs, and
  • Open-zone dwellings with a single thermostat

are treated identically. EN 12831 is control-agnostic because it is a design-day sizing standard, not an operational or energy-use model.

A central misconception addressed in this document is the belief that equal room temperatures imply no internal air movement. In reality, airflow is driven by pressure differences, not temperature differences. Even in open-zone homes with uniform setpoints, internal air movement persists due to:

  • Windward and leeward façade pressure differences,
  • Extract ventilation in kitchens and bathrooms,
  • Stack effect through stairwells and vertical spaces,
  • Uneven leakage paths and door positions.

As a result, internal air continues to redistribute heat between rooms, even when temperatures are equal. This redistribution increases individual room heat loss calculations but does not increase the net building heat loss.

Key conclusion: Under EN 12831-1:2017, it is correct and intentional that:
The sum of room ventilation heat losses exceeds the total zone or building ventilation heat loss.

Introduction

This article helps explain to heating engineers (boilers and heat pumps) why the sum of room heat losses differs from the total zone/building heat loss in EN 12831-1:2017.

The total sum of all rooms heat loss will be bigger than the zone/building heat loss.

Many heating engineers are still very confused why this is the case. This is mainly because the zone/building calculation applies the zone ventilation reduction factor fᵢ,z = 0.5 in Equation (16) (highlighted below).

Figure 1 ref: EN12831-1:2017
Figure 1 ref: EN12831-1:2017

The justification for not including this fi-z factor of 0.5 in equation 17 for determining each room ventilation heat loss is to allow for windward/leeward impacts and the loss of heated air moving to adjacent/parallel rooms.

Therefore, the internal movement of warm air from one room to another does not need to be factored in when sizing the heat source from the total zone/building heat loss. EN 12831 applies fi-z = 0.5 to represent the fact that, at zone/building level, a portion of air exchange is retained within the ventilation zone (e.g., windward/leeward effects and inter-room transfer), and should not be counted as net loss to outside.

Why does the sum of room heat losses exceed the building heat loss?

EN 12831 sizes rooms and the building heat source for different purposes.

Room heat losses are calculated for worst-case local conditions. Each room emitter must be able to cover:

  • External ventilation and infiltration, and
  • Internal air leaving the room to adjacent spaces.

For this reason, no reduction factor is applied at room level (Equation 17).

Building (zone) heat loss is calculated only for heat that actually leaves the building envelope. Air moving between rooms stays inside the heated zone and does not represent a net heat loss.

To avoid double-counting this internally retained heat, EN 12831 applies the zone ventilation reduction factor:

fᵢ,z = 0.5 (Equation 16)

This applies:

  • Whether rooms are controlled individually with TRVs (Figure 3), or
  • Whether the dwelling operates as a single open zone with one thermostat (Figure 5).

Control strategy does not change the calculation logic. EN 12831 is a design-day sizing standard, not an operational model.

Key rule: The sum of room ventilation heat losses will always be greater than the total zone/building ventilation heat loss — by design.

Figure 2 Ref: Schematic illustrating wind-driven natural ventilation and pressure distribution
Figure 2 Ref: Schematic illustrating wind-driven natural ventilation and pressure distribution, after Building Research Station / BRE, as reproduced in CIBSE Guide A and related UK building-physics literature.

Illustrating a building with Zone control with TRV’s

Figure 3: Zone controlled with TRV's
Figure 3: Zone controlled with TRV's

An incorrect representation

This diagram figure 4, is assuming there is no Pressure driven internal air movements even with equal temperature. This is NOT the case. Figure 4 shows a common incorrect assumption. Figure 5 shows the corrected representation.

Figure 4: Open zone (No TRV's, one room thermostat)
Figure 4: Open zone (No TRV's, one room thermostat)

Pressure-driven internal air movement (even with equal temperatures)

Even with:

  • one thermostat
  • no TRVs
  • uniform setpoint

There are still pressure differences caused by:

  • extract fans (bathroom / kitchen)
  • windward vs leeward façades
  • stack effect via stairwells
  • door positions
  • leakage distribution

Internal air movement does not disappear just because temperatures equalise.

In almost every dwelling:

  • Air is extracted from bathrooms / kitchens
  • Replacement air comes from other rooms
  • Even in an open zone.

Internal air movement does not disappear just because temperatures equalise.

Equal room temperatures do not imply zero internal air movement or zero internal heat transfer on the design day.

Illustration of an open zone system with no TRV’s.

Equal room temperatures do not imply zero internal air movement or zero internal heat transfer on the design day.

Figure 5 Equal room temperatures do not imply zero internal air movement or zero internal heat transfer on the design day
Figure 5 Equal room temperatures do not imply zero internal air movement or zero internal heat transfer on the design day

Still confused? Why your intuition says this, but physics says that.

What intuition tells us

It feels logical to assume that:

  • If all rooms are heated together
  • If all rooms are at the same temperature
  • If there are no TRVs and only one thermostat
  • then there should be no air movement between rooms, and therefore
  • the sum of room heat losses should equal the total building heat loss.

This intuition comes from thinking about temperature only.

What physics actually says

Air does not move because of temperature alone.

Air moves because of pressure differences.

Even in an open-zone dwelling with uniform temperatures, pressure differences still exist due to:

  • Wind acting on different façades (windward vs leeward)
  • Extract ventilation in kitchens and bathrooms
  • Stack effect via stairwells and vertical spaces
  • Uneven leakage paths in the building envelope
  • Doors being open or partially closed

As a result:

  • Air continues to move between rooms
  • Warm air leaves some rooms and enters others
  • Heat is redistributed internally even when temperatures are equal

The critical distinction

Internal air movement:

  • Does move heat between rooms
  • Does not remove heat from the building

Heat loss only occurs when air crosses the external envelope.

This is why EN 12831:

  • Sizes rooms conservatively (each room must cover its own worst-case losses)
  • Reduces building-level ventilation heat loss using the fᵢ,z factor, to avoid double-counting internally retained heat

Why controls don’t change this

Heating controls (TRVs, single thermostat, zoning) affect when and how often rooms are heated.

They do not eliminate:

  • Wind pressure
  • Ventilation-induced airflow
  • Stack-driven air movement

EN 12831 is therefore intentionally control-agnostic:

It sizes for the worst-case physical conditions, not typical operation.

For more technical articles visit the blog

View All Articles